A. one voltmeter and one ammeter
B. one voltmeter, one ammeter and one wattmeter
C. one voltmeter, one ammeter and one energy meter
D. any of the above
Related Mcqs:
- In a single phase power factor meter the phase difference between the currents in the two pressure coils is___________________?
A. exactly 0°
B. approximately 0°
C. exactly 90°
D. approximately 90° - In a 3-phase power measurement by two wattmeter method, both the watt meters had identical readings. The power factor of the load was___________?
A. unity
B. 0.8 lagging
C. 0.8 leading
D. zero - In a 3-phase power measurement by two wattmeter method the reading of one of the wattmeter was zero. The power factor of the load must be_______________?
A. unity
B. 0.5
C. 0.3
D. zero - The two pressure coils of a single phase power factor meter have_________________?
A. the same dimensions and the same number of turns
B. the same dimension but different number of turns
C. the same number of turns but different dimensions
D. none of the above - The use of _________ instruments is merely confined within laboratories as standardizing instruments?
A. absolute
B. indicating
C. recording
D. integrating
E. none of the above - In a dynamometer 3-phase power factor meter, the planes of the two moving coils are at_____________?
A. 0°
B. 60°
C. 90°
D. 120° - Commonly used instruments in power system measurement are_______________?
A. induction
B. moving coil or iron
C. rectifier
D. electrostatic - Induction type single phase energy meters measure electric energy in_______________?
A. kW
B. Wh
C. kWh
D. VAR
E. None of the above - The power of a n-phase circuit can be measured by using a minimum of_______________?
A. (n – 1) wattmeter elements
B. n wattmeter elements
C. (n + 1) wattmeter elements
D. 2n wattmeter elements - In a low power factor wattmeter the compensating coil is connected_______________?
A. in series with current coil
B. in parallel with current coil
C. in series with pressure coil
D. in parallel with pressure coil